OCCUPANCY SENSORS

INSTALLATION GUIDE

Line Switching Power Pack

Installer’s Specifications

Storage Temperature

-29° to 65°C (-20° to 150°F )

Operating Temperature

0° to 40°C (32° to 104°F)

Maximum Humidity

90% RH non-condensing

AC Power Input

120/277 VAC ± 10%, 60 Hz

Output Voltage

24 VDC

Output Current

100 mA max.

Relay Contacts:

Horsepower Rating

1 HP@120V

Switching Capacity

120 VAC, 60 Hz; 15 A tungsten 1800 W

277 VAC, 60 Hz 20 A Ballast

AA47

AA47

OPERATION

The AA47 Line-Switching Power Pack provides local switching capability to control
loads based on the signal from MSC Series occupancy sensors, independently of any
connection to building control systems. The AA47 routes 120/277 VAC, 60 Hz line
power directly to a Form A relay contact (SPST, normally open) to control a load,
and it generates full-wave, 24 VDC to power up to four MSC sensors (depending on
model). The relay is rated for maximum 15 A tungsten and 20 A ballast loads.

Mounted the AA47 either inside or outside a standard junction box using a 1/2-in.,
threaded EMT nipple. Route power to the sensor(s) using plenum-rated cable.

INSTALLATION

1. Provide separate overcurrent protection in accordance with the National Electrical

Code® and applicable local codes.

2. Use copper wire only.

3. Confirm that the device rating is appropriate for your application.

4. Set the voltage selector on the front of the unit to either 120 or 277 V, depending

on your application. The unit is shipped with the selector set to 277 V.

5. Mount the power pack to a suitable junction box using the 1/2-in., threaded nipple

and lock. The power pack is plenum-rated, and can be mounted to the inside or

the outside of a junction box or fixture in a ceiling plenum.

6. Connect the power pack as shown. Use approved wire nuts for electrical

connections.

120V

277V

RED

Load

Ext. Override OFF

RED

BLK

BLK

White

Neutral

Hot

BLUE

Control Input

Common

+24VDC

Voltage Selector

Sensor

Line Voltage
120/277VAC

From Sensor Output

Line Voltage

INSIDE

From Sensor Output

Line Voltage

OUTSIDE

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION

Failure to follow these instructions will result in death or serious injury.

DANGER

SCHEMATIC DIAGRAM

SYSTEM DIAGRAM

Hot

Voltage
Selector

Transformer

Red
(+24 VDC)

Black
(Common)
Blue
(Control)

Control

Load

Red

Relay

Neutral

White

Line Voltage
120/277 VAC

Black

MOUNTING OPTIONS