Installation guide, Configuration – Veris Industries H704-42_1(H)(E) Install User Manual

Page 6

Advertising
background image

6%2)3

H704

INSTALLATION GUIDE

Z202366-0M

page 6

©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]

02081

configuration

1

1

2

4

8

16 32 64 128

O

N

1

1. Communications Configuration: Communications parameters for the H704

series are field selectable for your convenience. Please see Product Diagram
section for selector location. The following parameters are configurable:

Parity On or Off

Parity: Odd or even

Wiring: Two or four

Baud Rate: 2400, 4800, 9600 or 19200

The values of each dip switch are as follows:

1=1
2=2
3=4
4=8
5=16
6=32
7=64
8=128

To determine an address you simply add the values of any switch that is on.

For example:

or

H704 series can be addressed as any whole number between and including 1-247.

Each unit is equipped with a set of 8 dip switches for addressing. See below.

LSB

MSB

VALUE

Example: 2-wire 9600 Baud No Parity (Default Only)

=

=

1
X
X
X
X
X
X

2

On

Off

3

Off

On

Off

On

4

Off
Off

On
On

5

6

7
X
X
X
X
X
X

8
X
X
X
X
X
X

2400 Baud
4800 Baud
9600 Baud
19200 Baud

2 wire
4 wire

Wiring, Baud Rate, Parity

Wiring

None
Even
Odd

Off
Off
On

Off
On
Off

Parity

Baud Rate

DESIRED RESULT

Switch #

Baud Rate and Parity Switch Setttings

40

2. Address Configuration: Each Modbus device on a single network must have a

unique address. The switch block must be set to assign a unique address before the
device is connected to the Modbus RS485 network. If an address is selected which
conflicts with another device, neither device will be able to communicate.

Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.
(8+32 = 40)

See the Communications Setup section for a pictorial listing of the first 63 switch
positions.