Caution, Installation guide, Operation – Veris Industries H921 Install User Manual

Page 2: Troubleshooting, Scaling, Wiring, Veris industries, H921, For load currents less than sensor minimum rating

Advertising
background image

VERIS INDUSTRIES

INSTALLATION GUIDE

H921

Z201166-0E

PAGE 2

©2010 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]

01101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

opEration

The H921 is a current transducer that senses current (amperage) in any of three
field-selectable ranges; zero-to-thirty, zero-to-sixty, or zero-to-one hundred twenty
amperes. These ranges represent the maximum current that can be applied to the
monitored conductor. The H921 transforms the monitored current into 4-20mA DC
output suitable for connection to building controllers or other appropriate data
acquisition equipment. The H921 requires 12-30VDC external power to generate its
output.

The H921 housing offers unprecedented mounting flexibility. The mounting bracket
can be attached in three different places. Additionally, the bracket is compatible with
the Veris AH01 DIN Rail clip, allowing DIN mounting.

notEs

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.

3x

1A

DANGER: 5A CTs can present hazardous voltages.

Install CTs in accordance with manufacturer's instructions.

Terminate the CT secondary before applying current.

H68xx‑5A CT

240A

300A:

5A

4A

> 120A (Sensor max.)

For load currents greater than sensor maximum rating:

Use a 5 Amp (H68xx series) Current Transformer (CT) as shown.

CAUTION

RISK OF EQUIPMENT DAMAGE

• Derate the product’s maximum current for the number of turns

through the sensing window using the following formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor

• Failure to follow these instructions can result in overheating

and permanent equipment damage.

Controller must be
programmed to account for the
extra turns. e.g., if three turns
pass through the sensor (as
shown) the normal controller
reading must be divided by 3.

< 3 A (Sensor Min.)

troublEshooting

Problem

Solution

No Reading at Controller

•Confirm that you have 12-30VDC in series with the

sensor output terminals and the control panel analog

input

• Assure that sensor core mating surfaces are clean and

that the core clamp is completely closed.

• Check polarity of sensor output connections

scaling

Set range switch.

1.

External Power

Sourcing Panel

(‑Common)

Sinking Panel

(+Common)

DDC

CONTROLLER

12-30VDC

Power Supply

AI

120

60

30

DDC

CONTROLLER

AI

COMM

4-20mA Out

120

60

30

DDC

CONTROLLER

AI

V(COM)

4-20mA
in Return

120

60

30

*A resistor can be added in parallel to convert the 4‑20mA signal to a VDC signal (250 ohm=
1‑5VDC); (500 ohm = 2‑10VDC)

Wiring

120

60

30

Amperage Range
Selector Switch

120

60

30

Scale controller

2.

software to match
selected output.

SENSED AMPS

Selected Range*

4mA

0A

20mA

SENSOR OUTPUT

*Factory calibrated ranges selected

with the amperage range switch

Advertising