Veris Industries HW PROTOCOL SERIES Datasheet User Manual

Modbus and bacnet protocol communication, Hw protocol series, Hu midit y

Advertising
background image

HU
MIDIT

Y

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Deluxe Wall Humidity &

Temperature Sensor,

Protocol Communication

FEATURES

Embedded BACnet and Modbus communication protocols...compatible with

many existing control systems

Configurable to multiple baud rates

Humidity and temperature sensors in one device at one address...provides

more information and maximizes system capacity

Pushbutton override capability from the building control system...local control

in individual rooms to maximize comfort

Innovative self-calibration algorithm...maximizes performance

Field calibratable

Thin-film capacitive sensor element recovers from 100% saturation

Fully interchangeable element to 1% or 2% accuracy...no calibration

Calibration-free interchangeable NIST traceable HS element

HS element is microprocessor profiled with on-board nonvolatile memory

Multi-point digital calibration to NIST standards

NIST certification available

Replace element in the field...minimizes field calibration downtime

DESCRIPTION

HW Protocol Series Deluxe humidity transmitters provide an ideal solution for
measuring relative humidity in all conditions. All devices are equipped with a
thin-film capacitive sensor that is easily replaceable in the field. These sensors are
calibrated to NIST standards, with certificates available.

The HWLP features embedded BACnet and Modbus communication protocols with
humidity and temperature sensing capability. The setpoint slider and pushbutton
override offer additional local control.

The wall-mounted HWLP model features a low-profile housing with an LCD display
for local indication. All models come with a standard five-year warranty.

APPLICATIONS

Office buildings, schools, or other systems utilizing BACnet or Modbus protocol

SPECIFICATIONS

Input Power

12 to 30VDC, 24VAC; 100mA max.

Housing Material

High impact ABS plastic , UL 94 VO

Communication:

Protocol

BACnet or Modbus (selectable)

Connection

2-wire RS-485

Data Rate

9600, 19200, 38400, 57600 (Modbus), bps (selectable); 9600, 19200, 38400, 76800 (BACnet), bps (selectable)

Parity

None/Odd/Even (selectable-Modbus); None (BACnet)

Address Range 1-127

Humidity:

HS Element

Replaceable digitally profiled thin-film capacitive; (32-bit mathematics); U.S. Patent 5,844,138 †

Accuracy*

±2% from 10 to 80% RH; NIST traceable multi-point calibration

Reset Rate**

24 hours

Stability

±1 @20°C (68°F) annually for two years

Hysteresis

1.5% typical

Operating Humidity Range

0 to 100% RH noncondensing

Operating Temperature Range

10° to 35°C (50° to 95°F)

Temperature Coefficient

±0.1% RH/°C above or below 25°C (typical)

Operating Environment:

Operating Temperature Range

10° to 35°C (50° to 95°F)

Temperature Transmitter Option:

Sensor Type

Solid-state, integrated circuit

Accuracy

±0.5°C (±1°F) typical

Resolution

0.1°C (0.2°F)

Range

10° to 35°C (50° to 95°F)

Setpoint Slider Resolution Option

1% full scale

Override Button Option

Remotely readable and resettable

† The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.

* Specified accuracy with 24VDC supplied power with rising humidity.
** Reset rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.

Note: RTD/Thermistors in wall packages are not compensated for internal heating of product.

EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2007 specification requirements)

Modbus and BACnet

Protocol Communication

HWLP

HW PROTOCOL SERIES

HQ0001723.B 01131

Advertising