Veris Industries E51H5A Install User Manual

Page 32

Advertising
background image

ZL0123-0A

Page 32 of 32

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 09132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E51H2A, E51H5A

TM

Troubleshooting

China RoHS Compliance Information
(EFUP Table)

部件名称

产品中有毒有害物质或元素的名称及含量Substances

铅 (Pb) 汞 (Hg)

镉 (Cd)

六价铬 (Cr(VI))

多溴联苯(PBB)

多溴二苯醚(PBDE)

电子线路板

X

O

O

O

O

O

O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下.

X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.

Z000057-0A

Problem

Cause

Solution

The maintenance wrench

icon appears in the power

meter display.

There is a problem with

the inputs to the power

meter.

See the Alert sub-menu or the Diagnostic Alert BACnet Binary_Input objects

The display is blank after

applying control power to

the meter.

The meter is not receiving

adequate power.

Verify that the meter control power is receiving the required voltage.
Verify that the heart icon is blinking.
Check the fuse.

The data displayed is

inaccurate.

Incorrect setup values

Verify the values entered for power meter setup parameters (CT and PT ratings,

system type, etc.). See the Setup section.

Incorrect voltage inputs

Check power meter voltage input terminals to verify adequate voltage.

Power meter is wired

improperly.

Check all CTs and PTs to verify correct connection, PT polarity, and adequate power.

See the Wiring Diagrams section for more information.

Cannot communicate

with power meter from a

remote personal computer.

Power meter address is

incorrect.

Verify that the meter is correctly addressed. See the Setup section.

Power meter baud rate is

incorrect.

Verify that the baud rate of the meter matches that of all other devices on its

communications link (see Setup section).

Communications lines are

improperly connected.

Verify the power meter communications connections. See the Communications

section.

Verify the terminating resistors are properly installed on both ends of a chain of

units. Do not use a terminator on units in the middle of a chain.

Verify shield ground connection between all units.