Veris Industries PW2 SERIES Datasheet User Manual

Wet media differential pressure transducer, 20 ma, 2-wire device, Pw2 series

Advertising
background image

PRESSURE

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

4-20 mA, 2-Wire Device

Wet Media Differential

Pressure Transducer

DESCRIPTION

The PW2 Series 2-wire, 4-20mA wet/wet pressure transducers incorporate

microprocessor profiled sensors for exceptional accuracy and reliability. Easy to use

and designed to provide exceptional installation savings, the PW2 Series is ideal for

measuring pressure across pumps, filters, heat exchangers, compressors, and other

non-corrosive wet media applications.

APPLICATIONS

●

Monitoring and controlling pump differential pressure

●

Chiller/boiler differential pressure drop

●

CW/HW system differential pressure

FEATURES

●

The jumper-selectable output switch for normal (4-20mA) or reverse

(20-4mA) operation provides application flexibility

●

Rugged, die-cast enclosure provides NEMA 4 sealing

●

Selectable differential units: psid or bard

●

Dual sensor design for improved overpressure tolerance... eliminates

the requirement for a bypass valve assembly in most applications

●

Jumper-controlled electronic surge dampening for high stability

●

Pushbutton zero calibration – no trim pots to adjust......maintain

accuracy and prevent callbacks with automatic zero calibration

●

Jumper-selectable port swap feature eliminates costly replumbing when

the high and low ports are improperly plumbed...change the jumper

position from normal to swap – problem solved!

●

Switch-selectable pressure ranges...fewer models to order and stock

●

LCD displays high pressure, low pressure, and differential pressure

with easy readability

Microprocessor provides digital signal conditioning

●

Noise rejection reduces fluctuating readings due to noise or turbulence

●

Surge damping prevents false alarms by averaging fast peaks

SPECIFICATIONS

Input Power

12 to 24VDC, loop powered

Maximum Current Draw 29mA

Output

2-wire transmitter; user selectable 4-20mA (clipped and capped) †

Accuracy @ 25°C*

Range A, B, C: ±1% F.S.; Range D: ±2% F.S.**

Surge Damping

Electronic; 5-second averaging

Pressure Ranges (Selectable):

0-50 psi (0-3.45 bar)

0-5/10/25/50 psid (0-0.34/0.69/1.72/3.45 bard)

0-100 psi (0-6.89 bar)

0-10/20/50/100 psid (0-0.69/1.38/3.45/6.89 bard)

0-250 psi (0-17.24 bar)

0-25/50/125/250 psid (0-1.72/3.45/8.62/17.24 bard)

Product Operating Environment

-10° to 55°C (14° to 130°F); 0 to 90%RH noncondensing

Long Term Stability

±0.25% per year

Zero Adjust

Pushbutton auto-zero

Housing Material

White powder-coated aluminum

Sensor:

Media Compatibility

Media compatible with 17-4 PH stainless steel

Proof Pressure

Max. 2x F.S. range

Burst Pressure

Max. 5x F.S. range

Temperature Compensated Range

0° to 50°C (32° to 122°F); TC Zero <±1.5% of product F.S. per sensor ; TC Span<±1.5% of product F.S. per sensor, (2 sensors per unit)

Media Temperature Limits

-20° to 85°C (-4° to 185°F); 0 to 90% RH non-condensing

Fittings

1/8" NPT female thread, 17-4 PH stainless

† Minimum input voltage: 250 Ω loop = 12VDC; 500 Ω loop = 17VDC
* Accuracy combines linearity, hysteresis, and repeatability. ** FS is defined as full span of selected range in bi-directional mode.
EMC Conformance: Low voltage directive 2006/95/EC; EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

Year

Warranty

5

PW2

0

Actual Pressure
Digitally Conditioned Output

TIME

F.S.

PRESSURE

Noise Rejection

Surge Damping

Output Clamping

PW2 SERIES

HQ0001832.B 01131

Advertising