Veris Industries H938 SERIES Datasheet User Manual

Current switches with relay: adjustable trip point, Status and control in one package, Typical coil performance

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Status And Control In

One Package

DESCRIPTION

The Hawkeye Relay Combination Series is the ideal solution for the automation

installer. These units combine a current switch and relay into a single package,

reducing the space required for total control of fans and pumps. The current

switch and relay operate independently of one another. These devices allow

start/stop control and status monitoring with one device instead of two.

APPLICATIONS

●

Starting/stopping and monitoring positive status of motors

●

Detecting belt loss and coupling shear

FEATURES

●

Combines command relay and fan/pump status sensor in a single, easy to install

unit

●

Reduces number of components installed...fits better in small starter enclosures

●

Detect belt loss and motor failure...ideal for fan and pump status

●

H748 and H948 feature a SPDT command relay...control two outputs with a

single relay

●

Bracket on H938, H948, and H958 can be installed in three different

configurations...added flexibility

●

Reduced charges from electrician

●

Relay and status LEDs for easy setup

●

Polarity insensitive status output...fast and easy installation

●

Adjustable setpoint for current sensor status...fits many applications

●

5-year warranty

Maximize Reliability

Minimize Installed Cost

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Hysteresis

10% Typical

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing

Do not use the LED status indicators as evidence of applied voltage.

Current Switches with Relay:

Adjustable Trip Point

Year

Warranty

5

Voltage

AC

DC

24V................................... 10mA

10mA

12V.................................................................... 20mA

TYPICAL COIL PERFORMANCE

Hx38, Hx58 (SPST, N.O.)
Resistive
..................................10A@250VAC, 30VDC
Inductive.................................5A@250VAC, 30VDC

H735 (SPST, N.O.)
Resistive
..................................5A@250VAC, 30VDC
Inductive.................................3A@250VAC, 30VDC

RELAY CONTACT RATINGS

Hx48 (SPDT)
Resistive
.................................. 8A@250VAC, 30VDC
Inductive................................. 3.5A@250VAC, 30VDC

Pull In Voltage
Hx3x .............................................................. 20.1VDC
Hx48 .............................................................. 20.1VDC
Hx58 .............................................................. 8.4VDC
Drop Out Voltage
Hx3x .............................................................. 5.2VDC
Hx48 .............................................................. 5.2VDC
Hx58 .............................................................. 3.0VDC

H738

H938

H738 & H938 SERIES

TM

DETECTS BELT LOSS/COUPLING SHEAR!

DETECTS BELT LOSS/COUPLING SHEAR!

Now you can easily detect when drive belts slip, break, or pump couplings shear.

In fact, a typical HVAC motor that loses its load has a reduction of current draw

of up to 50%. That’s why our sensors are the industry standard for status.

Calibrated

Trip Point

Off

Off

Fan/pump

On

Loss of Belt/Coupling Shear

Electrical

Failure

HQ0001760.B 01131

Advertising