Veris Industries AA14A Datasheet User Manual

Year, Aa14a & aa16a, Ac cess ories

Advertising
background image

A

c

cess

ories

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

AA14A

Bypass Manifold and Mounting

Bracket for PW Sensors

Easy Installation for Wet Media

Pressure Sensing Applications

AA14A & AA16A

DESCRIPTION

The AA14A/AA16A Bypass Valve Assembly is designed for easy installation and
maintenance of Veris PW or PW2 Series wet media pressure transmitters. The AA16A,
when ordered with the PW, comes with the bracket and manifold connected, for an
easy, one-step installation. The AA14A includes a bracket and manifold assembly that
is connected to the PW in the field.

AA16A

Year

Warranty

5

DIMENSIONAL DRAWINGS

ORDERING INFORMATION

HQ0001905.A 01121

COMMISSIONING

1. Close valves C and A before beginning.

2. Open B (null).

3. Open D (bleed or purge).

4. Slowly open A to bleed air from line.

5. Close B, then fully open A.

6. Slowly open C to bleed air from line.

7. Close D, then fully open C.

MAINTENANCE

1. Close A and C to isolate pressure sensor.

2. Open B (null) to equalize pressure.

3. Open D (bleed or purge).

B A

C

D

B

A

C

D

B A

C

D

Valve positions: All closed

Valve positions: All open

Valve positions: Normal operation

6.75”

(172 mm)

8.7”

(221 mm)

8.7”

(221 mm)

7.75”

(191 mm)

1.8”

(46 mm)

3.5”

(89 mm)

3.5”

(89 mm)

0.5”

(13 mm)

1.5”

(38 mm)

1.5”

(38 mm)

MODEL

DESCRIPTION

AA14A

Bypass Valve Assembly (PW/PW2 sold separately; customer connects to mounting

bracket)

AA16A

Bypass Valve Assembly with PW/PW2 connected (PW/PW2 must be ordered

separately)

Advertising