Veris Industries V121 SERIES Datasheet User Manual

Enclosed victory relays: 20a spst, with hoa switch, Hoa switch provides local control, Typical coil performance contact ratings

Advertising
background image

REL

AY

S

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

APPLICATIONS

●

Command contactors

●

Control motors

●

Isolation

●

Device interlocking

●

Relay logic

●

Sense voltages for alarm conditions

FEATURES

●

Sleek field enclosure reduces the need for panel space

●

The nipple mount feature allows the V121 Series to be mounted to any

electrical enclosure

●

Flexible tinned stranded wire...fits easily in tight spaces and provides secure

connections to wire nuts

●

UL508 Listed...designed and approved for field installation...makes electrical

inspection a snap

●

Products include a cover that conceals and protects the HOA switch, reducing the

likelihood of tampering

●

Limit costly control system override & service calls

●

The switch position monitors available with the V122/V222 & V123/V223

models allow the control system to notify the building owner when a motor is

inadvertently left ON or OFF

DESCRIPTION

The Victory 121, 122, and 123 Series HOA relays have a concealed HOA switch for
local control and troubleshooting with limited unauthorized switch manipulation.
To further guard against control system override, the V122/V222 and V123/V223
are equipped with a monitored HOA. The V122/V222 provides a two-wire resistive
output and the V123/V223 offers a three-wire digital monitor. Now you can enjoy
the convenience of local control with none of the drawbacks.

SPECIFICATIONS

Operating Temperature Range

-40° to 60°C (-40° to 131°F)

Operating Humidity Range

10-90% RH non-condensing

Expected Relay Life

Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles

Relay Status

LED ON=energized

Wire Specifications:

Lead Length

14” (356 mm) min.

Gauge

UL1015; Coil: 18 AWG; Contacts: 12 AWG; HOA monitor wires: 16 AWG

Insulation Class

277VAC RMS

V122/V222 Resistive Monitor Maximums:

Voltage Max.

13.4VAC/DC

Current Max.

4mA AC/DC

V123/V223 Digital Monitor Maximums:

Dry Circuit Contact Rating (Max.) 24VAC/DC@100mA

Agency Approvals

UL 508

Enclosed Victory Relays:

20A SPST, with HOA Switch

Year

Warranty

5

HOA Switch Provides

Local Control

V122/222

V121/221

Cover conceals

HOA switch

Voltage

Coil Current

AC

DC

24V.......................................... 75mA

32mA

120V........................................ 42mA

-

208V........................................ 36mA

-

277V........................................ 49mA

-

TYPICAL

COIL PERFORMANCE

CONTACT RATINGS

V121, V221
Resistive
.............. 20A@240VAC

8A@28VDC

14A@14VDC

Motor.................... 1HP@120VAC
V122, V123, V222, V223
Resistive
.............. 20A@240VAC

8A@28VDC

14A@14VDC

Motor.................... 1HP@250VAC

VICTORY 121, 122, & 123 SERIES

HQ0001841.B 01131

Advertising