24

5 Connecting to power supply

VEGAPULS 63 • 4 … 20 mA/HART - four-wire

36512-EN-130228

Fig. 16: Connection steps 5 and 6

5. Insert the wire ends into the terminals according to the wiring plan
Information:

Solid cores as well as flexible cores with cable end sleeves are

inserted directly into the terminal openings. In case of flexible cores

without end sleeves, press the terminal head with a small screwdriver;

the terminal opening is freed. When the screwdriver is released, the

terminal closes again.
6. Check the hold of the wires in the terminals by lightly pulling on

them

7. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation in case of power

supply via low voltage

8. Connect the lead cable for power supply in the same way accord-

ing to the wiring plan, in addition connect the ground conductor to

the inner ground terminal when powered with mains voltage.

9. Tighten the compression nut of the cable glands. The seal ring

must completely encircle the cables

10. Screw the housing cover back on
The electrical connection is hence finished.
Information:

The terminal blocks are pluggable and can be removed from the

housing insert. To do this, lift the terminal block with a small screwdriv-

er and pull it out. When inserting the terminal block again, you should

hear it snap in.

5.3 Wiring plan, double chamber housing

The following illustrations apply to the non-Ex as well as to the Ex-d

version.