9 maintenance and fault rectification, 1 maintenance, 2 rectify faults – VEGA VEGADIF 65 Profibus PA User Manual
Page 67
![background image](/manuals/263945/67/background.png)
67
9 Maintenance and fault rectification
VEGADIF 65 • Profibus PA
36129-EN-130417
9 Maintenance and fault rectification
9.1 Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.
In some applications, product buildup on the separating diaphragms
can influence the measuring result. Depending on the sensor and
application, take precautions to ensure that heavy buildup, and espe-
cially a hardening thereof, is avoided.
9.2 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
VEGADIF 65 offers maximum reliability. Nevertheless, faults can oc-
cur during operation. These may be caused by the following, e.g.:
•
Sensor
•
Process
•
Voltage supply
•
Signal processing
The first measures to be taken are to check the output signals as well
as to evaluate the error messages via the display and adjustment
module. The procedure is described below. Further comprehensive
diagnostics can be carried out on a PC with the software PACTware
and the suitable DTM. In many cases, the causes can be determined
and the faults rectified this way.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since
we offer this service world-wide, the support is only available in the
English language. The service is free of charge, only the standard
telephone costs will be charged.
The following table describes possible errors and helps to remove
them:
Error
Cause
Rectification
When an addi-
tional instrument
is connected, the
segment fails.
Max. supply
current of the seg-
ment coupler
exceeded
Measure the current consumption, re-
duce size of segment
Wrong pres-
entation of the
measured value in
Simatic S5
Simatic S5 cannot
interpret the num-
ber format IEEE
of the measured
value
Insert converting component from Sie-
mens
Maintenance
Reaction when malfunc-
tions occur
Failure reasons
Fault rectification
24 hour service hotline
Checking Profibus PA