6 Adjustment with the display and adjustment module PLICSCOM

VEGADIF 65 • 4 … 20 mA

36236-EN-130417

Damping

Linearization curve

Leak flow volume suppression

Sensor-TAG

Displayed value

Display unit

Scaling

Current output

Unit of measurement

Language

The following safety-relevant data are not uploaded or downloaded:

HART mode

PIN

Copy sensor data

Copy sensor data?

Basic adjustment

The reset "Basic adjustment" resets the values of the following menu

items to the reset values (see chart):

Menu section

Menu item

Reset value

Basic settings

Zero/Min. adjustment

Measuring range begin

Span/Max. adjustment

Measuring range end

Density

1 kg/l

Density unit

kg/l

Damping

1 s

Linearization

Linear

Sensor-TAG

Sensor

Display

Displayed value

Differential pressure

Display unit

Mass/kg

Scaling

0.00 to 100.0

Decimal point indication 8888.8

Diagnostics

Totalizer

0.0000 10

00

gal

Part sum counter

0.0000 10

00

gal

Service

Current output - charac-

teristics

4 … 20 mA

Current output - failure

mode

< 3.6 mA

Current output - min.

current

3.8 mA

Current output - max.

current

20.5 mA

The values of the following menu items are not reset with "Reset: