VEGA VEGADIF 65 4 … 20 mA User Manual
Page 49
![background image](/manuals/264189/49/background.png)
49
6 Adjustment with the display and adjustment module PLICSCOM
VEGADIF 65 • 4 … 20 mA
36236-EN-130417
•
Damping
•
Linearization curve
•
Leak flow volume suppression
•
Sensor-TAG
•
Displayed value
•
Display unit
•
Scaling
•
Current output
•
Unit of measurement
•
Language
The following safety-relevant data are not uploaded or downloaded:
•
HART mode
•
PIN
Copy sensor data
Copy sensor data?
Basic adjustment
The reset "Basic adjustment" resets the values of the following menu
items to the reset values (see chart):
Menu section
Menu item
Reset value
Basic settings
Zero/Min. adjustment
Measuring range begin
Span/Max. adjustment
Measuring range end
Density
1 kg/l
Density unit
kg/l
Damping
1 s
Linearization
Linear
Sensor-TAG
Sensor
Display
Displayed value
Differential pressure
Display unit
Mass/kg
Scaling
0.00 to 100.0
Decimal point indication 8888.8
Diagnostics
Totalizer
0.0000 10
00
gal
Part sum counter
0.0000 10
00
gal
Service
Current output - charac-
teristics
4 … 20 mA
Current output - failure
mode
< 3.6 mA
Current output - min.
current
3.8 mA
Current output - max.
current
20.5 mA
The values of the following menu items are not reset with "Reset:
Reset