VEGA VEGADIF 65 4 … 20 mA User Manual

Page 73

Advertising
background image

73

10 Supplement

VEGADIF 65 • 4 … 20 mA

36236-EN-130417

Tantalum diaphragm

Measuring cell

10 mbar

30 mbar

100 mbar

500 mbar

Influence of the sys-

tem pressure to the

zero point

±0.28 % of

URL/7 bar

±0.70 % of

URL/70 bar

±0.42 % of

URL/70 bar

±0.14 % of

URL/70 bar

Influence of the sys-

tem pressure to the

span

±0.28 % of

URL/7 bar

±0.70 % of

URL/70 bar

±0.42 % of

URL/70 bar

±0.14 % of

URL/70 bar

Measuring cell

3 bar

16 bar

40 bar

Influence of the system

pressure to the zero point

±0.14 % of URL/7 bar

±0.14 % of URL/70 bar

±0.14 % of URL/70 bar

Influence of the system

pressure to the span

±0.14 % of URL/7 bar

±0.14 % of URL/70 bar

±0.14 % of URL/70 bar

Total accuracy
Total Performance - Basic version
The specification "Total Performance" comprises non-linearity incl. hysteresis and non-repeatability,

thermal change of the zero point and static pressure influence (p

st

= 70 bar).

Total Performance

Ʋ 316L, Alloy, gold-rhodium diaphragm ±0.15 % of the set span

13)14)

Ʋ Tantalum diaphragm

±0.30 % of the set span

15)16)

Total Error - basic version
The specification "Total Error" comprises the longterm stability and the total performance.

Diaphragm material

Measuring range

Total Error

316L, Alloy, gold rhodium

< 500 mbar

0.33 % of the measuring range end

value/year

from 500 mbar

0,20 % of the measuring range fi-

nal value

Tantalum

< 500 mbar

0.48 % of the measuring range end

value/year

from 500 mbar

0.35 % of the measuring range end

value/year

Heating time - all versions
Warm-up time

≤ 10 s

Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue cur-

rent output 4 … 20 mA. Specifications refer to the measuring range final value.

Measuring ranges

1 year

5 years

10 mbar, 100 mbar

±0.18 %

-

13)

For measuring ranges ≥ 500 mbar to TD 2 : 1

14)

All specifications apply to the temperature range +10 … +60 °C (+50 … +140 °F).

15)

For measuring ranges ≥ 500 mbar to TD 2 : 1

16)

All specifications apply to the temperature range +10 … +60 °C (+50 … +140 °F).