VEGA VEGADIF 65 4 … 20 mA User Manual

Page 70

Advertising
background image

70

10 Supplement

VEGADIF 65 • 4 … 20 mA

36236-EN-130417

Adjustment range of the zero/span adjustment relating to the nominal measuring range:

Ʋ Pressure value zero

-120 … +120 %

Ʋ Pressure value span

zero + (-220 … +220 %)

7)

Adjustment level
Adjustment range of the min./max. adjustment relating to the nominal measuring range:

Ʋ Percentage value

-10 … +110 %

Ʋ Pressure value

-120 … +120 %

8)

Adjustment flow
Adjustment range of the zero/span adjustment relating to the nominal measuring range:

Ʋ Pressure value zero

-120 … +120 %

Ʋ Pressure value span

-120 … +120 %

9)

Recommended max. turn down

15 : 1 (no limitation)

Nominal measuring ranges, measurement limits and smallest spans to be calibrated

Nominal range

Lower measurement

limit

Upper measuring limit

Smallest adjustable

span

10 mbar (1 kPa)

-10 mbar (-1 kPa)

+10 mbar (+1 kPa)

0.25 mbar (25 Pa)

30 mbar (3 kPa)

-30 mbar (-3 kPa)

+30 mbar (+3 kPa)

0.3 mbar (30 Pa)

100 mbar (10 kPa)

-100 mbar (-10 kPa)

+100 mbar (+10 kPa)

1 mbar (100 Pa)

500 mbar (50 kPa)

-500 mbar (-50 kPa)

+500 mbar (+50 kPa)

5 mbar (500 Pa)

3 bar (300 kPa)

-3 bar (-300 kPa)

+3 bar (+300 kPa)

30 mbar (3 kPa)

16 bar (1600 kPa)

-16 bar (-1600 kPa)

+16 bar (+1600 kPa)

160 mbar (16 kPa)

40 bar (4000 kPa)

-40 bar (-4000 kPa)

+40 bar (+4000 kPa)

400 mbar (40 kPa)

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characterstic curve

Linear

Calibration position of the measuring cell Vertical, i.e. upright process component
Influence of the installation position to the

zero point

≤ 4 mbar

10)11)

A position-dependent zero-point shift can be corrected (see also chapter "Adjust parameter").
Position of the span in the measuring

range

Based on the zero point

Diaphragm material

316L, Alloy C276, gold rhodium plated, Monel

7)

Values less than -1 bar cannot be set.

8)

Values less than -1 bar cannot be set.

9)

Values less than -1 bar cannot be set.

10)

Max. value with horizontal process component. Specification applies to the basic version without chemical seal.

The value doubles with instruments with inert oil.

11)