48

7 Set up with the display and adjustment module

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

43387-EN-131119

Menu

Menu item

Default value

Setup

Measurement loop name

Sensor

Isotope

Cs-137

Application

Summation Slave

Outputs

Deactivated

Adjustment

0 %, 100 %

Linearization

0 ct/s ≙ 100 %
90000 ct/s ≙ 0 %

Background radiation

0 ct/s

Unit of the process value

%

Temperature unit

°C

Damping

60 s (manually)

Real value correction

0

Current output

Deactivated

Current output mode

4 … 20 mA, < 3.6 mA

Current output Min./Max.

Min. current 3.8 mA, max. current 20.5 mA

Reference value - Relay

None

Mode

Overfill protection

Upper switching point -

Process value

0 %

Lower switching point -

Process value

0 %

Upper switching point -

Temperature

50 °C

Upper switching point -

Temperature

25 °C

Block adjustment

Released

Address - Summation

Slave

free

Display

Language

Selected language

Displayed value

Pulse rate

Display unit

ct/s

Additional adjustments

Temperature unit

°C

Linearisation curve

Empty

HART mode

Standard
Address 0

7.5 Parameter adjustment - Point level detection

The instrument is adapted to the application conditions via the pa-

rameter adjustment. The parameter adjustment is carried out with an

adjustment menu.