3 rectify faults – VEGA SOLITRAC 31 4 … 20 mA_HART - four-wire With SIL qualification User Manual

Page 67

Advertising
background image

67

9 Diagnostics and service

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

43387-EN-131119

Code
Text mes-

sage

Cause

Rectification

S017
Accuracy

outside the

specification

– Accuracy outside the

specification

– Correct adjustment data

S025
Bad lineariza-

tion table

– Bad linearization table

– Carry out linearization

S038
Slave outside

the specifica-

tion

– Slave outside the specifica-

tion

– Check Slave

S125
Ambient tem-

perature too

high/too low

– Ambient temperature too

high/too low

– Protect instrument with

isolating material against

extreme temperatures

The instrument has no status messages to the section "Maintenance".

9.3 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

The first measures are:

Evaluation of fault messages, for example via the display and

adjustment module

Checking the output signal

Treatment of measurement errors

Further comprehensive diagnostics options are available with a PC

with PACTware and the suitable DTM. In many cases, the reasons can

be determined in this way and faults rectified.

Connect a multimeter in the suitable measuring range according to

the wiring plan. The following table describes possible errors in the

current signal and helps to remove them:

Error

Cause

Rectification

4 … 20 mA signal

not stable

Level fluctuations Set damping according to the instru-

ment via the display and adjustment

module or PACTware/DTM

Maintenance

Reaction when malfunc-

tions occur

Procedure for fault recti-

fication

Check 4 … 20 mA signal

(level measurement)