Quick start

The quick start procedure enables a quick setup of the instrument

with many applications. You can find further information in the respec-

tive chapters of the operating instructions manual.
1. Distance from the metallic vessel wall > 300 mm. Distance from

non-metallic vessel wall > 500 mm. The probe must not touch any

installations or the vessel wall.

2. In non-metallic vessels, place a metal sheet beneath the process

fitting.

1

2

Fig. 1: Installation in plastic silo
1 Flange

2 Metal sheet

3. If necessary, fasten probe end.
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-

tions on the type label.

2. Connect the instrument according to the following illustration

5

0

0

5

1

6

2

7

3

8

4

9

0

5

1

6

2

7

3

8

4

9

1

0

1

6 7 8

Bus

2
3

4

5

1

2

+

( )

(-)

1

Fig. 2: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output

2 For display and adjustment module or interface adapter

3 Selection switch for bus address

4 For external display and adjustment unit

5 Ground terminal for connection of the cable screen

For further information see chapter "Connecting to power supply".

For standard applications we recommend selecting the "Quick setup"

in the display and adjustment module.

Mounting

Electrical connection

Set parameters