VEGA VEGAFLEX 82 Profibus PA User Manual

Page 37

Advertising
background image

37

6 Set up with the display and adjustment module

VEGAFLEX 82 • Profibus PA

44220-EN-130910

Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Deflectors, etc.

Note:

A false signal suppression is only recommended with liquid applica-

tions.
A false signal suppression detects, marks and saves these false sig-

nals so that they are no longer taken into account for level measure-

ment.
This should be done with the lowest possible level so that all potential

interfering reflections can be detected.
Proceed as follows:

Enter the actual distance from the sensor to the product surface.

All interfering signals in this section are detected by the sensor and

stored.
Note:

Check the distance to the product surface, because if an incorrect

(too large) value is entered, the existing level will be saved as a false

echo. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,

the following menu window appears when selecting "False signal

suppression":

Setup - False signal sup-

pression

Advertising