Measurement error during filling – VEGA VEGAFLEX 82 Profibus PA User Manual

Page 65

Advertising
background image

65

9 Diagnostics and service

VEGAFLEX 82 • Profibus PA

44220-EN-130910

Wherever the sensor displays a constant value, the reason could

also be the fault setting of the current output to "Hold value"

In case of a too low level indication, the reason could be a line

resistance that is too high

Measurement error with constant level

Fault description

Error pattern

Cause

Rectification

1. Measured value

shows a too low or too

high level

Leve

l

time

0

– Min./max. adjustment not

correct

– Adapt min./max. adjustment

– Wrong linearization curve

– Adapt linearization curve

2. Measured value

jumps towards 100 %

Level

time

0

– Due to the process, the ampli-

tude of the product echo sinks

– A false signal suppression was

not carried out

– Carry out a false signal sup-

pression

– Amplitude or position of a

false echo has changed (e.g.

condensation, buildup); false

signal suppression no longer

matches

– Determine the reason for the

changed false echoes, carry

out false signal suppression,

e.g. with condensation

Measurement error during filling

Fault description

Error pattern

Cause

Rectification

3. Measured value

jumps towards 0 %

during filling

Level

time

0

– Amplitude of a multiple echo

(vessel top - product surface) is

larger than the level echo

– Check parameter "Application",

especially vessel top, type

of medium, dished end, high

dielectric constant, adapt if

necessary

– The level echo cannot be distin-

guished from the false echo at

a false echo position (jumps to

multiple echo)

– In case of interferences due to

installations in the close range:

Change polarisation direction

– Chose a more suitable installa-

tion position

– Transverse reflection from an

extraction funnel, amplitude of

the transverse reflection larger

than the level echo

– Direct sensor to the opposite

funnel wall, avoid crossing with

the filling stream

4. Measured val-

ue fluctuates around

10 … 20 %

Level

time

0

– Various echoes from an uneven

product surface, e.g. a material

cone

– Check parameter "Type of

medium" and adapt, if neces-

sary

– Optimize installation position

and sensor orientation

– Reflections from the product

surface via the vessel wall

(deflection)

– Select a more suitable installa-

tion position, optimize sensor

orientation, e.g. with a swivel-

ling holder