6 Set up with the display and adjustment module
VEGAFLEX 82 • Profibus PA
44220-EN-130910
In menu item "Scaling unit" you define the scaling variable and the
scaling unit for the level value on the display, e.g. volume in l.
In menu item "Scaling" you define the scaling format on the display
and the scaling of the measured level values for 0 % and 100 %.
Level measured value min.
Measured level value max.
To damp process-dependent measured value fluctuations, you can
set a time of 0 … 999 s in this menu item.
The damping applies to the level and interface measurement.
The default setting is a damping of 0 s.
In the menu item "Lock/unlock adjustment", you can protect the
sensor parameters against unauthorized modification. The PIN is
activated/deactivated permanently.
The following adjustment functions are possible without entering the
PIN:
•
Select menu items and show data
•
Read data from the sensor into the display and adjustment mod-
ule.
Setup - AI FB1 - Scaling
unit
Setup - AI FB1 - Scaling
Setup - AI FB1 - Damping
Lock/release setup - Ad-
justment