0 mA … 20 mA/4 mA … 20 mA transmitter
This system can be used if the field device requires a relatively
high voltage. A 250 Ohm resistance is connected in parallel
with the Ex-output of the 10 V/50 Ohm output of this 2-channel
barrier. Thus a voltage of 15.5 V is available at the field device
if the voltage supply is 27 V. The system is approved for
[EEx ia] IIC.
The combination of a 28 V, 300 Ohm and a 28 V barrier with
diode return is the solution for applications with 3-wire
transmitters. Special attention must be paid here to the internal
voltage drop. The reason for this is the diode return. The
system is approved for [EEx ia] IIC.