19 zener barriers - operating instructions, Application examples, Hazardous area safe area – VEGA Z728 Zener barriers User Manual

Page 19: Harzardous area safe area

Advertising
background image

19

Zener barriers - operating instructions

Application examples

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

Da

te of issu

e

05/2

3

/03

Potentiometric position detection

Applications in which the accuracy is not critical can be
satisfied as shown above. The intrinsically safe circuit has a
direct connection to ground. An additional resistance on this

side would have an effect on the voltage signal and would have
to be taken into account. The system is approved for [EEx ia]
IIC.

If greater accuracy is required, a 4-wire solution must be
applied. The Z715 Zener barrier transfers the power supply to
the potentiometer, whilst two Z715.1K barriers transfer the

signal to the receiver. The supply voltage in the example above
could be 13 V.

Hazardous area

Safe area

V

Z960

x3

x3

x3

1

2

3

4

8

7

6

5

Harzardous area

Safe area

Signal

Z715

x3

CL

1

2

8

7

Z715.1K

x3

CL

1

2

8

7

Z715.1K

x3

CL

1

2

8

7