3zener barriers - operating instructions, Multi-channel barriers, Hazardous area safe area – VEGA Z728 Zener barriers User Manual

Page 3: 2 multi-channel barriers, 3 grounding of zener barriers

Advertising
background image

3

Zener barriers - operating instructions

Multi-channel barriers

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

Da

te of issu

e

05/2

3

/03

1.2

Multi-channel barriers

Analogue circuits are often connected to two-channel barriers
(see Figure 1.5). Since there is no grounding on this type of
circuit, the system is a quasi floating one. It is termed "quasi
floating", because it is "one Zener voltage" above the ground
potential. Although it does not actually float, the signal-to-noise
ratio is improved.

A further advantage of multi-channel Zener barriers is that a
higher packing density can be achieved.

.

Figure 1.4

Single-channel Zener barrier

Figure 1.5

Two-channel Zener barrier

1.3

Grounding of Zener barriers

Intrinsically safe circuits with Zener barriers without galvanic
isolation must be grounded. The cross-section of the ground

connection, using a copper conductor, must be at least 4 mm

2

(for further details see EN 60079-14, section 12.2.4). The
maintenance of these requirements prevents the occurrence of
a dangerous potential with respect to ground.

A fault of the type illustrated in figure 8.6 can cause a
dangerous spark if the Zener barrier is not grounded, but
grounding is provided via the field device in the intrinsically
safe circuit (Figure 1.5). If a potential occurs in the fault case,
which is higher than permitted (see Figure 1.6) the Zener
diodes become conducting and the current is conducted away
via the ground. The fuse "blows".

.

Figure 1.6

Non-grounded Zener barrier

Figure 1.7

Grounded Zener barriers
The system must have its own independent ground
conductor, through which no supply system current
flows.

Power supply can
not be grounded.

Hazardous area

4 mA ... 20mA

transmitter

Safe area

24 V

R

M

(+)

Hazardous area

4 mA ... 20mA

transmitter

Safe area

24 V

R

M

(+)

Fault

Transformer

Hazardous potential

Hazardous potential

Power supply

AC/DC
supply
voltage

Hazardous
area

Safe area

Fault

Transformer

Power supply

Hazardous
area

Safe area

Fault current

Intrinsically
safe ground

Advertising