Milton CAT 3512C 1500 kW 1875 kVA 60 Hz 1800 rpm 480 Volts Performance Data User Manual
Page 6

EMISSIONS DATA
EPA TIER-2 2006 - *************************************************** B5
Gaseous emissions data measurements are consistent with those described in
EPA 40 CFR PART 89 SUBPART D and ISO 8178 for measuring HC, CO, PM, and NOx
Gaseous emissions values are WEIGHTED CYCLE AVERAGES and are in compliance
with the following non-road regulations:
LOCALITY AGENCY/LEVEL MAX LIMITS - g/kW-hr
----------------- ------------ -----------------------------------
U.S. (incl Calif) EPA/TIER-2 CO:3.5 NOx + HC:6.4 PM:0.2
REFERENCE EXHAUST STACK DIAMETER
8 IN
WET EXHAUST MASS
21,100.4 LB/HR
WET EXHAUST FLOW (762.80 F STACK TEMP )
11,071.16 CFM
WET EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )
4,321.00 STD CFM
DRY EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )
3,958.78 STD CFM
FUEL FLOW RATE
105 GAL/HR
Page 6 of 10
Performance Data
12/04/2009