Milton CAT 3512C 1500 kW 1875 kVA 60 Hz 1800 rpm 480 Volts Performance Data User Manual
Page 7

RATED SPEED "Not to exceed data"
GEN
PWR
EKW
PERCENT
LOAD
ENGINE
POWER
BHP
TOTAL
NOX (AS
NO2)
LB/HR
TOTAL
CO
LB/HR
TOTAL
HC
LB/HR
PART
MATTER
LB/HR
OXYGEN
IN
EXHAUST
PERCENT
DRY
SMOKE
OPACITY
PERCENT
BOSCH
SMOKE
NUMBER
1,500
100
2206 28.9800
3.9500
.7100
.2000 10.2000
.8000
1.2800
1,125
75
1662 14.7100
2.4400
.7800
.2000 11.5000
.9000
1.2800
750
50
1144
9.6800
3.3200
.7400
.3000 12.2000
1.9000
1.2800
375
25
632
7.2600
4.0700
.5800
.3800 13.2000
3.3000
1.2800
150
10
310
5.6300
3.8300
.6700
.2300 15.2000
2.0000
1.2800
RATED SPEED "Nominal Data"
GEN
PWR
EKW
PERCENT
LOAD
ENGINE
POWER
BHP
TOTAL
NOX (AS
NO2)
LB/HR
TOTAL
CO
LB/HR
TOTAL
HC
LB/HR
TOTAL
CO2
LB/HR
PART
MATTER
LB/HR
OXYGEN
IN
EXHAUST
PERCENT
DRY
SMOKE
OPACITY
PERCENT
BOSCH
SMOKE
NUMBER
1,500
100
2206 24.1500
2.1900
.5300
2,262.3
.1400 10.2000
.8000
1.2800
1,125
75
1662 12.2600
1.3600
.5900
1,764.4
.1400 11.5000
.9000
1.2800
750
50
1144
8.0700
1.8400
.5500
1,242
.2100 12.2000
1.9000
1.2800
375
25
632
6.0500
2.2600
.4400
720
.2700 13.2000
3.3000
1.2800
150
10
310
4.6900
2.1300
.5000
410.8
.1600 15.2000
2.0000
1.2800
Page 7 of 10
Performance Data
12/04/2009
http://tmiweb.cat.com/tmi/servlet/TMIDirector?Action=buildtab&refkind=RNTMIRefNu...