Series 2000 Autoflow Operation

Series 2000 Autoflow Operation

Series 2000 Autoflow Operation

Series 2000 Autoflow Operation

Series 2000 Autoflow Operation

2 0

ERROR MESSAGES

ERROR MESSAGES

ERROR MESSAGES

ERROR MESSAGES

ERROR MESSAGES

Fan 2 Housing High Limit

The temperature high limit located on the

housing on fan and heater number two opened, indicat-
ing that the housing towards the bin has overheated.
This high limit sensor is set at 200 degrees Fahrenheit
and must be manually reset.

Fan 3 Housing High Limit

The temperature high limit located on the

housing on fan and heater number three opened,
indicating that the housing towards the bin has over-
heated. This high limit sensor is set at 200 degrees
Fahrenheit and must be manually reset.

Plenum High Limit

An over temperature condition has occurred

inside the dryer plenum. The plenum high limit is set
automatically on the Hi-lo thermostat when the cycle
set-point is adjusted and resets automatically when
cooled. The lo-fire gas pressure needs to be lowered,
or the cycle setpoint on the Hi-lo thermostat needs to
be increased if the error is displayed frequently.

Fan 1 Motor Overload

The thermal overload in the control box on fan

number one has tripped, indicating an overcurrent
condition. The overload must be reset manually.

Fan 2 Motor Overload

The thermal overload in the control box on fan

number two has tripped, indicating an overcurrent
condition. The overload must be reset manually.

Fan 3 Motor Overload

The thermal overload in the control box on fan

number three has tripped, indicating an overcurrent
condition. The overload must be reset manually.

Fan 1 Loss Of Airflow

The contacts on the airswitch, located in the

bin sidewall and attached to fan and heater number
one, have opened due to the fan not turning, or the
airswitch may need to be adjusted.

Drying Chamber Overflow

The grain level in the drying chamber has

reached the drying chamber overflow rotary switch.
Grain will have to be dumped from the drying chamber
to the storage chamber before the unit can be restarted.
This error indicates that either the drying chamber high
level rotary switch is faulty or the time on the Load
delay or Aux. 1 delay needs to be lowered.

Bin Grain High Limit Full

The grain level in the storage chamber has

reached the storage chamber high level rotary switch
located 3 feet below the fan and heater(s). Grain will
have to be removed from the storage chamber before
the unit can be restarted.

Bin High Limit Switch Bad

The storage chamber high level switch has

failed. Both the normally open and the normally
closed sides of the switch are in the same state.

Out Of Grain

The grain in the wet supply tank has fallen

below the wet supply rotary switch. If there is grain
against the drying chamber low level rotary switch the
dryer can be restarted by pressing the stop switch to
clear the error and then the start switch.