Heater orifice setup, Installation – Grain Systems PNEG-1775 User Manual

Page 18

Advertising
background image

5. Installation

18

PNEG-1775 Vane Axial Heater - Canadian

Heater Orifice Setup

The factory has set the orifices size for propane, high temperature and natural gas, low temperature.

1. Determine the type of gas to be used: Propane or natural gas.

2. Determine the operating temperature ranges to be used: High or low. Refer to tables on

Page 22

and

Page 23

.

3. For natural gas high temperature applications remove reducer bushing with pressure gauge and

remove primary orifice from system. Replace reducer bushing and check connections for leaks.
For natural gas high temperature configuration there is no primary orifice in the system. Refer to

Fuel - Temperature Table below.

4. For propane low temperature applications remove reducer bushing with pressure gauge and replace

the supplied primary orifice with orifice supplied in control box. Replace reducer bushing and check
connections for leaks. Refer to

Fuel - Temperature Table below.

Figure 5G

Fuel - Temperature

Fuel

Temperature

High

Low

Natural Gas

Remove primary orifice completely.

No modifications required.
Standard with 7/32" orifice.

Propane

No modifications required.
Standard with 7/32" orifice.

Replace primary orifice with 3/32"
orifice supplied in control box.

CAUTION

Make sure the configuration matches the appropriate application in the

Fuel - Temperature Table above.

Propane has a higher BTU content than natural gas.

Do not remove 3/8" secondary orifice. Excessive heat rise due to improper orifice
sizing or removing the 3/8" secondary orifice will damage grain or cause fire.