PNEG-119 Inline Centrifugal Fan

13

5. Fan Installation

Figure 5A

Previously Installed Units

It is recommended that previously installed units be checked to see that a machine to earth ground has
been installed by an electrician.

Machine to Earth Ground

It is very important that a machine to earth ground rod be installed at the fan. This is true even if there is
a ground at the pole 15 feet (15') away. This ground needs to be as close to the fan as possible, but no
more than 8 feet (8') away. The ground rod should be connected to the fan control panel with at least a #6
solid bare copper ground wire or in accordance with local requirements. The machine to earth ground
provides additional safety if there is a short. It also provides the grounding necessary for long life and
operation of the solid state.

Cross-sectional area of phase conductors

supplying the equipment S (mm

2

)

Minimum cross-sectional area of the external

protective conductor S (mm

2

)

S<=16

S

16<=S<35

16

S=>35

S÷2

Use a #6 or approved size bare copper ground wire. Install a 5/8" diameter 8' long
copper-clad ground rod, 2' away from the foundation and 1' below the surface of the
ground or in accordance with local requirements.