Maxfire, Series 100 gas igniters – Forney MAXFire 100 User Manual

Page 2

Advertising
background image

MAXFire

®

Series 100 Gas Igniters

Specifications

Fuel:

Natural gas or propane

Minimum Length:

14 inches

Guide Tube Material:

10 & 30 - Stainless steel

35, 40 & 50 - Carbon steel with 12” stainless steel at furnace end

MAXFire

Model

Capacity

MBtu/hr

Guide

Tube OD

Connections (NPT)

Cooling Air

Requirement*

Nozzle

Type

Typical Fuel

Pressure (psig)

Gas

Air

110

0.3 to 1.5

1 7/8”

1/2”

3/4”

23 @ 3

Straight

5-12

130

1.5 to 6.0

2 7/8”

3/4”

3/4”

45 @ 3

Straight or wide

5-12

135

5.0 to 15

3 1/2”

1 1/2”

1 1/2”

50 @ 6

Straight or wide

5-25

140

5.0 to 25

4”

1 1/2”

1 1/2”

80 @ 6

Straight or wide

5-25

150

10 to 50

5”

TBD

TBD

120 @ 6

Straight or wide

5-25

*scfm@inches w.c. above windbox

HESI Specifications

Input Voltage:

120 to 240 VAC, 50/60 Hz

Input Power:

120 VAC @ 1.5 A (2-A fuse); 240 VAC @ 0.75A (1-A fuse)

Output Voltage:

2000 VDC

Output Energy:

12 joules per spark

Spark Rate:

3 per second (approximately)

Duty Cycle:

50% at temp 0°F to 135°F (-18°C to 57°C) Ambient

HTSI Specifications

Amperage:

20 mA

Input Voltage:

120 to 240 VAC 50/60 HZ

Output Voltage:

6000 VAC

Duty Cycle:

100% at temperature rating

Primary Combustion Zone

Clamp

Guide Tube

Cooling/combustion Air Inlet

Gas Inlet

HESI

Pub # 404006-19

Rev 01/2011

Forney Corporation • 3405 Wiley Post Road • Carrollton, TX 75006 • 800-356-7740 • Fax 972-458-6650 • www.forneycorp.com