Forney MAXFire 40 Low Pressure User Manual

Page 2

Advertising
background image

Forney Corporation
3405 Wiley Post Road
Carrollton, TX 75006 USA
Tel: 972.458.6100
Fax: 972.458.6650
www.forneycorp.com

IGNITERS

MAXFIRE SPECIFICATIONS

Fuel:

Natural gas

Fuel Pressure:

1.5 psig (0.103 bar)

Maximum Length:

10 feet (304.8 cm)

Guide Tube Material:

Carbon steel with 12 inches stainless steel at furnance end

MAXFire

CAPACITY

GUIDE TUBE COOLING AIR REQUIREMENT

TIP

MODEL

MBTU/HR OD

(ABOVE WINDBOX)

TYPE

40

6.0

4.0 inches

60 scfm @ 6 inches wc

Straight nozzle

101.6 mm

1.7 m3/min @ 14.9 mbar

For other sizes and capacities consult the factory.

HESI SPECIFICATIONS
Input Voltage:

120 to 240 VAC 50/60 HZ

Output Voltage:

2000 VDC

Output Energy:

12 joules per spark

Spark Rate:

3 per second (approx.)

Duty Cycle:

50% at – 18 to 57°C (0 to 135°F)

HTSI SPECIFICATIONS
Amperage:

20 mA

Input Voltage:

120 to 240 VAC 50/60 HZ

Output Voltage:

6000 VDC

Input Current:

1.5 A (2-A fuse); 240 VAC @ 0.75A (1-A fuse)

Duty Cycle:

100% at temperature rating

TECHNICAL BULLETIN

PUBLICATION
#404006-18

REV 06/06