COOLING CHAMBER FOR IDD SERIES DETECTORS

PRODUCTS AND ACCESSORIES

Cooling Chamber

Part #381071-01

IDD II, Filtered Infrared Detector

Part #38321-21

IDD-IIU, Unfiltered Infrared Detector

Part #38321-22

IDD-IIL, Infrared Detector for Lignite

Part #339234-01

SPECIFICATIONS

The Forney Cooling Chamber is required when the ambient temperature is above 140°F

(60°C) but no more than 200°F (93°C).

Dimensions:

9.8” x 5” x 3.5” (249 x 127 x 89mm)

We i g h t :

4 lbs 2oz (1.86kg)

Mounting:

1" FNTP sight tube fitting

Cooling air connection:

1" FNTP

Materials:

Cast Steel Housing, Silicone Rubber Seal

Electrical:

N/A

Detector temperature limits:

32°F to 140°F (0°C to 60°C) for all IDD detectors

Cooling air flow/supply:

Front mount applications - minimum cooling air flow of 10 scfm

(17m

3

/hr) at a maximum temperature of 120°F (48°C)

Fiber optic applications - minimum cooling air flow of 15 scfm

(25m

3

/hr) at a maximum temperature of 120°F (48°C)

Compatible flame detectors: IDD-II, IDD-IIU, IDD-UV and IDD- I I L

Cable support:

The cooling air chamber supports the IDD series detec-

tor cable by capturing it in the cooling air housing cap.