add 7/8” for mating connectors

The PM IDD 9000 is available as single or dual channel. The dual channel has
a separate, identical PCB motherboard for each channel. Each board contains
six connectors on the side panels. Dual channel shown, bottom board is re-

moved on single channel configuration.

14.00

1.75

6.50

LEFT SIDE VIEW

BACK

J1

J2

J3

J4

J5

J6

Channel 1

Channel 2

Panel Mount IDD 9000

Rack Mount IDD 9000

The RM IDD 9000 is a dual channel amplifier with a separate identical CPU
Processor for each channel. The right side is for Channel 1 and the left side

is Channel 2. The RM IDD 9000 is designed for installation into an amplifier
rack (Part # 404325-02) in an equipment cabinet.

IDD 9000 Flame Detector Amplifier

Products and Accessories:

Dual Channel Panel Mount (PM) IDD 9000 Amplifier

Part #408100-00

Single Channel Panel Mount (PM) IDD 9000 Amplifier

Part #408100-50

Rack Mount (RM) IDD 9000 Amplifier - dual channel

Part #408120-01

Amplifier Tuning Kit

Part #408103-01

Termiflex / SMARTDisplay

®

terminal with 9-pin connector*

Part #408106-01

Cable 40’ (for IDD)

Part #399854-04

Cable 40’ (for UV-4)

Part #399855-04

Compatible Flame Detectors:

IDD-II, Filtered, Infrared Detector

IDD-IIU, Unfiltered, Infrared Detector

IDD-IIL, Infrared Detector for Lignite

UV-4, UV Tube Detector

Part #38321-21
Part #38321-22
Part #38321-23
Part #379189-02

*

If using an older Termiflex / SMARTDisplay

®

terminal with a 25-pin connection, a DB25-pin to DB9-pin adapter is required (Forney Part #408107-01)

IDD 9000 Specifications:

Panel Mount:

Rack Mount:

Dimensions:

10 1/2” x 7 7/8” x 3 7/8” (26.6 cm x 20 cm x 9.8 cm)

6.5 x 14 x 1.75 inches (155.6 x 355.6 x 44.5 mm)

Weight:

5 lbs. 3 oz.

1 lb 7 oz.

Temperature:

32° to 140°F (0° to 60°C)

Humidity:

5% to 95% relative humidity, non-condensing

Power Requirements:

120/240 VAC, 50/60 Hz @ 12 VA

Output Relay Ratings (SPDT):

3 A at 125 VAC, 250 VAC & 30 VDC

3 relays are available for each channel (Lamp, Main Flame & Alarm).

Flame Strength:

4-20 mA or 0-10 VDC (sourcing)

Flame Failure Response Time (FFRT):

2.0, 3.0 or 3.8 seconds

Flame Pickup Time:

less than 2 seconds

Nonvolatile RAM:

8 complete operating profiles

Approvals:

Factory Mutual (FM)

Pub # 404005-21