Horn igniters – Forney Horn User Manual

Page 2

Advertising
background image

PACHE / FORNEY 1 / TECH BULLETINS WORKING / SCANS / HORN IGNITER

LINE ITEM #11 on Requsition # 42871

This is one of the original POSTSCRIPT files submitted by Larry Cawood back in May. Not a part of what Picas & Points received

7/27/95. If there is now a duplicate, please specify which to use by indicating USE THIS ONE or DESTROY THIS ONE.

USE THIS ONE per MERRILL 8/4/95.....

REVISED 9/12/95 PER MERRILL JONES

HESI

IGNITER

FRONTPLATE

OIL INLET

ATOMIZING AIR INLET

IGNITER HORN

(DIFFUSER)

FLAME

DETECTOR

OBSERVATION

PORT

OIL NOZZLE

IGNITER

WINDBOX

Pub # 404006-07

Rev 01/2011

Horn Igniters

Specifications

Fuel:

No. 2 Oil, Propane or Natural Gas

Oil

Capacity Rating:

2 – 4 MBtu (consult factory for higher output, available up to 15 MBtu)

Fuel Pressure:

60 – 125 psig

Atomizing Media Pressure:

25 psig differential over oil pressure

Gas

Capacity Rating:

2 – 4 MBtu (consult factory for higher output, available up to 15 MBtu)

Fuel Pressure:

12 – 25 psig

Cooling/Combustion Air

Flow:

120 SCFM

Pressure:

4 – 6 inches w.c. above furnace pressure

HESI Specifications:

Input Voltage:

120 to 240 VAC, 50/60 Hz

Input Power:

120 VAC @ 1.5 A (2-A fuse); 240 VAC @ 0.75A (1-A fuse)

Output Voltage:

2000 VDC

Output Energy:

12 joules per spark

Spark Rate:

3 per second

(approximately)

Duty Cycle:

50% at temp 0°F to 135°F ( -18°C to 57°C ) Ambient

Forney Corporation • 3405 Wiley Post Road • Carrollton, TX 75006 • 800-356-7740 • Fax 972-458-6650 • www.forneycorp.com