FLOOR PORTION

SEM 7820

Sentronic Electro-Magnetic

Single Door Holder Floor Mounted

®

4 9/16”

116mm

SINGLE DOOR INSTALLATION

CLEARANCE FOR SEM7820

FLOOR PORTION

LOCATION OF

CONDUIT

DOOR PIVOT

POINT

WALL

DOOR

WIDTH

(INCHES)

ARC LENGTH

4

6”

1
4

DIA.

®

1-800-526-2400

12/06 © 2006 SCHLAGE LOCK Company. All rights reserved D.P. # 29350

Step 1: Plan the Installation
A. Measure the door width.
B. Calculate the arc length by subtracting 5 5/8 from the door width.

Draw an arc at the calculated length using the door pivot point as
the center point. String and a pencil could be used to draw the arc
on the floor.

C. Open the door to the desired position. On the pull side of the door,

put a mark on the arc 4

from the door. This is the center of the

conduit hole.

D. Drill and install conduit as needed. Maximum conduit size is

.

Maximum conduit height above the floor is 1 .

E. Pull wire in accordance with applicable codes, standards, and

authorities having jurisdiction. Electrical specifications are
shown below.

¼”

½”

Input Voltage

Current Draw Max.

120VAC, 60Hz

.02A

24VAC, 60Hz/24VDC

.02A

12VDC

.03A

Step 2: Install the Magnet
A. The magnet is shipped partially assembled for protection. Unscrew the cover from the base, then unscrew the magnet bracket

assembly from the base. Keep the screws for later reattachment.

B. Guide the conduit through the hole in the base and snug up the conduit nut. Square up the base to the door, with the door

opened to the desired position, as shown in Fig.1.

C. See Fig. 2. Using the base as a template, mark the four mounting hole locations on the floor.
D. Remove the base and drill 3/8” holes in the floor at 1 1/4” deep. Install the cement anchors provided into the drilled holes,

threaded ends up.

E. Reposition the base, aligning the mounting holes with the floor holes and the magnet opening facing the door.

Tighten the conduit nut. Install (2)

mounting screws that are furthest away from the magnet opening into the cement anchors.

The magnet assembly must first be connected to power supply wires before the other two base housing mounting screws can be

installed.

F. See Fig. 3. Connect the supply earth ground wire to the green wire on the magnet assembly bracket. Connect the power supply

common wire to the screw terminal marked COM. If the supply voltage is 24V, connect the power supply hot wire to the screw
terminal marked 24V. If the supply voltage is 120V, connect the power supply hot wire to the screw terminal marked 120V. If the
supply voltage is 12V, connect the power supply hot wire to the screw terminal marked 12V. Polarity is important on the 12V input.

There are protective plastic tabs over the terminal screws. Break off the two tabs that protect COM and the desired voltage so that

the screw heads are exposed.

G. See Fig. 2. With the magnet wired, position the magnet bracket assembly over the two base mounting holes and the two base

post holes. Insert (2)

-20 base mounting screws

and the (2) 10-24 shorter screws from step 2A into

the post holes. Tighten firmly. Attach the cover using the (2) 10-24 longer screws from step 2A.

¼-20

into the cement anchors

¼

COM

24V

120V

12V

Earth Ground

5

5
8

5”

127mm

2 17/32”

64mm

2 7/8”

73mm

Fig. 1

Fig. 2

Back view of magnet assembly

IMPROPER INSTALLATION MAY

RESULT IN PERSONAL INJURY OR

PROPERTY DAMAGE. FOLLOW ALL

INSTRUCTIONS CAREFULLY. FOR

QUESTIONS, CALL LCN AT

800 - 526 - 2400

CAUTION

!

Fig. 3

MOUNTING

HOLES

CONDUIT

HOLE

Cover

Magnet
Bracket
Assembly

Base

Advertising