3.6 Electrical Installation
3.6.1 Power Connections
Cabling and Fusing
NB!
Cables General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper (75°C) conductors are recommended.
The power cable connections are situated as shown below. Dimensioning of cable cross section must be done in accordance with the current ratings and local
legislation. See the Specifications section for details.
For protection please see fuse in the tables of the fuse section. Always ensure that proper fusing is made according to local regulation.
NB!
Use a screened/armoured motor cable to comply with EMC emission specifications. For more information, see EMC specifications in the AF-650 GPDesign
Guide.
See section General Specifications for correct dimensioning of motor cable cross-section and length.
AF-650 GP High Power Operating Instructions