4.1.2 Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up procedure using Keypad (read table from
left to right). The example applies to open loop applications:
Press
Q2 Quick Set-Up
Set language
par. K-02 Motor Speed Unit
Set motor speed in Hz or RPM
par. P-02 Motor Power [HP] or par. P-07 Motor
Power [kW]
Set Motor nameplate power
par. F-05 Motor Rated Voltage
Set Nameplate voltage
Set Nameplate frequency
par. P-03 Motor Current
Set Nameplate current
par. P-06 Base Speed
Set Nameplate speed in RPM
Set reference source
par. F-02 Operation Method
Select which reference site to activate
Set the accel time with reference to synchronous motor speed, n
s
Set the decel time time with reference to synchronous motor speed,
n
s
Set motor thermal protection
par. F-15 Motor Speed High Limit [Hz] or par.
F-17 Motor Speed High Limit [RPM]
Set motor speed high limit in Hz or RPM
par. F-16 Motor Speed Low Limit [Hz] or par.
F-18 Motor Speed Low Limit [RPM]
Set motor speed low limit in Hz or RPM
Set allowed rotation direction
Set desired auto tune function. Enable complete auto tune is rec-
ommended