1 standard features 2-2 operating instructions, Power break® ii switches, 1 standard features – GE Industrial Solutions Power Break II Switches, 800-4000A Frames, 240-600Vac User Manual
Page 12: 2 operating instructions, Chapter 2. operation
Power Break® II Switches
Chapter 2. Operation
2-1 Standard Features
Power Break II switches are equipped with the following
standard features. The letters are keyed to the switch
photographs in Figures 6 and 7.
A Indicator:
ON
– Red
OFF
– Green
B Indicator:
CHARGED
– Yellow
DISCHARGED
– White
C
ON
button
D
OFF
button
E Manual charging handle
F Integral 36-point terminal block (12 auxiliary
switches, A-B type), Block “A”
G Integral 36-point terminal block (all other con-
nections), Block “B”
H Sealable hinged cover
I Cover mounting screws (4)
K Control Unit interchangeable rating plug
L Test set connection port
M Standard padlock provision
N Dust-resistant ventilation slots
4
Figure 6. Front of the switch, showing the locations of
standard features.
Figure 7. Front of the switch, with the Control unit and top
cover removed.
2-2 Operating Instructions
Sequence of Operations
The sequence of operations that may be performed on the
switch are listed in Table 3. Refer to Chapter 3 for
information about accessory operation.
Operating Instructions for Manually
Operated Switch
Charging the Mechanism Springs
Pull the operating handle down about 90° (until it stops).
Repeat five more times to fully charge the springs.
This
will not close the switch contacts.
The charge indicator
will show
CHARGED
on a yellow background. When the
springs are fully charged, the handle locks in the stored
position.
NOTE:
The switch cannot be closed unless the springs
are fully charged and the handle is stored fully in.
NOTE:
La fermeture de l'interrupteurne peut être réal-
isée à moins que les ressorts soient réarmés tout à fait, et
le levier est complètement remis à la position
d’emmagasinage.