Power Break® II Switches

Chapter 3. Accessory Operation

12

Catalog

Number

Voltage

Rating

Peak Inrush

Current, A

Nominal RMS

Current, mA

SPUV012DC 12

Vdc

19

300

SPUV024DC 24

Vdc

15

140

SPUV048DC 48

Vdc

7.5

70

SPUV125DC 125

Vdc

3

30

SPUV250DC 250

Vdc

1.5

15

SPUV024AC 24

Vac

15

370

SPUV048AC 48

Vac

7.5

210

SPUV120AC 120

Vac

3

80

SPUV208AC 208

Vac

1.9

60

SPUV240AC 240

Vac

1.5

45

SPUV480AC

480

Vac

0.75

20

SPUV600AC

600

Vac

0.60

16

24–600 Vac devices are rated for 50/60 Hz.
Peak inrush current is present for 2–6 ms after activation. This number is

provided so that fuses and supplies can be chosen appropriately.

Ratings for 480 Vac and 600 Vac devices are at the input of the upstream

transformer, included with the accessory and specified in GEH–6520,
which powers the device. For voltage and current ratings at the switch
terminal block, see SPUV120AC.

Table 13. Catalog numbers and voltages for the Undervoltage

Release.

3-8 Motor Operator Mechanism

The Motor Operator Mechanism, shown in Figure 18,
provides a means of remotely or automatically charging

the springs that close the switch. Table 14 lists the catalog

numbers for the available Motor Operator Mechanism

models. For installation instructions see GEH-6281.

Figure 18. Motor Operator Mechanism.

Catalog No.

Voltage Rating

SPE024 24

Vdc

SPE048 48

Vdc

SPE072 72

Vdc

SPE120 120

Vac

SPE125 125

Vdc

SPE240 240

Vac

Table 14. Catalog numbers and operating voltages for the

Motor Operator Mechanism.

Remote Operation

The switch closing springs can be charged remotely by
shorting terminals 17 and 35 on the terminal block on the

right side of the switch, with a push button or similar

device, for a minimum of five seconds.

Automatic Operation

Connect terminals 17 and 35 on the terminal block on the
right side of the switch with a jumper wire. The Motor

Operator will automatically recharge the switch closing

springs whenever the switch closes.

CAUTION:

Do not wire switches for both automatic

charge and automatic close.

ATTENTION:

Ne pas câbler les interrupteurs pour tous

les deux l’armement automatique et la fermeture

automatique.

3-9 Remote Close

The Remote Close accessory, shown in Figure 19, provides
a means of remotely closing the switch after the springs

have been charged. Table 15 lists the catalog numbers for

the available models. For installation instructions see

GEH-6283.

Remote Operation

The switch can be closed remotely, provided that the
springs are charged, by applying the rated voltage to

terminals 16 and 34 on the terminal block on the right

side of the switch.
The Remote Close accessory is continuously rated and has

an anti-pump feature that prevents a motor-operated

switch from repeatedly closing into a fault. Closing control

voltage must be removed and reapplied for each switch

closure.