Table 1 Wire Sizes and Torque Requirements for 460 VAC Panels
Table 2 UL508 Requirement- Tightening torque
Table A Redundant drive panel

In-Warranty Information Form

Table 1

Device

AF - 600 Hp Rating(s)

Minimum Wire

Size

Maximum

Wire Size

Required Torque

NON FUSED

DISCONNECTOR AND

FUSE BLOCK

15 through 30Hp

# 14 AWG

# 4 AWG

Note 1

40 through 50Hp

# 8 AWG

1/0

Note 1

60 through 75Hp

# 8 AWG

1/0

Note 1

100 through 125Hp

# 4 AWG

300 MCM

Note 1

FUSED DISCONNECTOR

15 through 30

# 10 AWG

# 3 AWG

Note 1

40 through 50

# 14 AWG

# 2/0 AWG

Note 1

60 through 100

# 6 AWG

# 3/0 AWG

Note 1

125 through 250

# 2 AWG

# 600MCM

Note 1

Drive output power

Terminal Board

15 through 25

# 10 AWG

# 7 AWG

16 lb.in

30 through 40

# 35 AWG

# 2 AWG

40 lb.in

50 through 75

# 50 AWG

1/0

89 lb.in

100

# 95 AWG

4/0

212 lb.in

125

# 120 MCM

250MCM

212 lb.in

Power Distribution Blocks

15 through 100

# 2/0 AWG

# 14 AWG

Note 1

125

# 350 (1) MCM

# 6 (1) AWG

Note 1

125

# 2 (3) AWG

# 14 (3) AWG

Note 1

Control Terminal Board

2 through 125

# 26 AWG

# 10 AWG

Note 1

Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file

Appendix B – Wire Sizes, Torque and Estimated Watt loss Details