DEH40635

AN 12-1007 Rev.02, 04/04/2012

Table 2

UL508 Requirement

Table 54.1 , Tightening torque for screws

Test wire size installed

in connector (AWG)

Tightening torque (lb in.)

Slotted head no 10 and large

Hexagonal head - external drive

socket wrench

Slot width - 0.047 inch

or less and slot length

1/4 inch or less

Slot width

- 0.047

inch or

slot

length -

over 1/4

inch

Split bolt connectors

other

connectors

18-10

20

35

80

75

8

25

40

80

75

6-4

35

45

165

110

3

35

50

275

150

2

40

50

275

150

1

-

50

275

150

1/0 - 2/0

-

50

385

180

3/0-4/0

-

50

500

250

250-350

-

50

650

325

400

-

50

825

375

500

-

50

825

375

600-750

-

50

1000

375

800-1000

-

50

1100

500

1250-2000

-

-

1100

600

Note : For values of slot width or length not corresponding to those specified, the largest torque

value associated with the conductor size shall be marked. Slot width is the normal design value.

Slot length shall be measured at the bottom of the slot