The environments for NEMA Type 1 enclosures shall be indoor where the

following condition may exist; falling dirt.


For all enclosure types the ambient temperature must remain in the
range from -10

C (14

F) to 40

C (104

F). Never store or operate panel

below or above ambient range. All wall-mounted enclosures must be

mounted on a non-flammable or heat resistant surface.


Some enclosure configurations of AF-600 Redundant Drive Panels require

ventilation to keep the components and inverter within their thermal

recommendations. The enclosure door and sides contains grilles at the

bottom and top to allow for air to circulate through the enclosure.

Ventilation is accomplished by the cooling fan(s) mounted at the bottom

grille(s) pulling air into the enclosure and forcing it out the top grille(s).

The air used for ventilating the enclosure must be free from condensation,

moisture, dirt, dust, and flammable or combustible vapors and/or dust

The recirculation of air leaving the enclosure should be avoided. Air

forced out of the enclosure should not be allowed to circulate back into

the enclosure. All enclosures shall be installed where the doors are able

to completely open. Do not mount enclosure where the air flow into or

out of it may be restricted.


INSTALLATION

Panels must be installed per NEC 110.26 and local codes and have
minimum clearance to operate door safely and allow for proper

maintenance as needed, (e.g., access and change filters).

Determine conduit entry and exit locations on the enclosure before
mounting. See the appropriate Outline drawing for recommended

conduit locations.

Allow for input and output power wiring to be located in separate conduit.

No conduit holes are provided in the enclosure; therefore the customer

must install all conduit holes. Place a protective covering over the

components of the panel while installing the conduit holes to prevent

metal shavings or chips from landing on part or electronic boards.

CAUTION: Damage to equipment will result if panel is operated or

stored below or above stated ambient temperature range.

.

WARNING: The temperature of the inverter heat sink fins may

reach 90

C (194

F). Thus if not mounted on a heat resistant or a non-

flammable surface a fire may occur resulting in a fatal or serious injury,
as well as damage to equipment.