Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

133

Table 9-A: Power System Troubleshooting Table

Controller

LED

User Interface

Display

Rectifier

LED

Distribution

Module

Board LED

Possible Problem(s)

Possible Solution(s)

RED

MIN, Rectifier
Fail

MAJ, Multiple
Rectifier Fail

MAJ, Battery on
Discharge

AC OK

ALARM

Normal

Multiple rectifier thermal
alarm: Excessive ambient
temperature

Multiple rectifier failure

1. Verify that there is no

obstruction of the vertical
airflow path.

2. Reset rectifies by removing

them, waiting approximately
30s and replacing them.

3. If problem persists, replace the

rectifiers.

4. If problem still persists, call

your local field representative.

RED

MAJ, High
Voltage

AC OK

ALARM

Normal

High output voltage from
rectifier(s)

Rectifier(s) high voltage
shutdown

Internal rectifier(s) failure

1. Reset the rectifier(s) by

removing the rectifier(s),
waiting approximately 30s and
replacing the rectifier(s).

2. If problem persists, replace the

rectifier.

3. If problem still persists, call

your local field representative.

Amber

MIN, Clock
Battery Low

AC OK

DC OK

Normal

Internal Lithium Battery Is
Low

1. The battery is not designed to

be easily field replaced. The
controller unit needs to be
replaced.

2. Obtain all desired information

such as alarm history,
statistics, and any field
configuration that is different
than the standard.

AMBER

MIN, Minor
Communication
Fail

RED

Blinking

Single

rectifier

GREEN

Rectifier lost
communication with
controller.

1. If a rectifier has been removed

from an installed/operational
system, go to the
Control/Operations menu and
execute Uninstall Equipment.

2. Reset the rectifier by removing

the rectifier, waiting
approximately 30 seconds, and
replacing.

3. If problem persists, replace the

rectifier.

4. If problem still persists, call

your local field representative.

RED

MAJ, Major
Communication
Fail

GREEN

RED

(Blinking)

LVD Board lost
communication with the
controller.

1. Replace Distribution Module

Board. (Note 2)

2. If problem persists, call your

local field representative.