Replacement procedures, continued – GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual
Page 80

Galaxy Power System 4848/100 with Dual Rectifier Shelf
11 - 8 Maintenance and Replacement
Issue 5 September 2011
Replacement Procedures, continued
Replacing the Rectifier Fan Assemblies, continued
Step
Action
6
Remove the fan cable clamps.
7
Carefully unplug the fan connectors (2). Fan connectors are
keyed and can be loosened by inserting a screwdriver into the
slotted side of the connector and gently prying the fan-side
connector loose.
8
Remove the fans by removing the fan screws (8).
9
Install the new fans in position as shown in Figure 11-2 by
installing the fan screws (8).
10
Position the fan cables as shown in Figure 11-2.
11
Replace the fan cable clamps.
Caution
Place faceplate ground wire terminal under fan cable
clamp as shown in Figure 11-2.
12
Replace the faceplate by installing the faceplate screws (4).
13
Install the rectifier, following the “Installing or Replacing a
Rectifier” procedure in this section.
14
Test replaced rectifiers using the “Testing Additional Alarms
After Replacement of Rectifiers” procedure in this section.