9 SPECIFICATIONS

Model

:

GT5000 GT6000 GT8000 GT10000

Ratings

Power ratings depending on input voltage

:

VA / W

VA / W

VA / W

VA / W

100V / 200V

:

4000 / 3400

4800 / 3400

6400 / 6400

8000 / 6400

110V / 220V

:

4500 / 3800

5400 / 3800

7200 / 7200

9000 / 7200

115V / 230V

:

5000 / 4000

6000 / 4200

8000 / 8000

10000 / 8000

120V / 208V

:

4800 / 4200

5200 / 4200

8000 / 6900

8700 / 8000

120V / 240V

:

5000 / 4200

6000 / 4200

8000 / 8000

10000 / 8000

127V / 220V

:

4800 / 4200

5200 / 4200

8000 / 6900

8700 / 8000

Input thermal circuit breaker (A)

:

30

30

60

60

Internal input fuse 250V, slow (A)

:

30

30

30*2

30*2

Input converter

AC input voltage

:

Nominal: 120 / 208 V

AC input voltage range

: 100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V

Input current waveform

:

sine wave

Input current (A) at nominal input voltage

:

20

20

40

40

Input power factor

:

> 0.97

Input frequency range

:

40 - 70 Hz

Input phase (L1 to L2)

:

120° / 180° / 240° ±10°

Inrush

current

:

40 40 40 40

Output converter

AC output voltage

:

100 / 110 / 115 / 120 / 127 V (selectable)

AC output voltage tolerance

:

L-N ± 3%; L1-L2 ± 5%

L-N ± 2%; L1-L2 ± 5%

Output frequency

:

50 / 60 Hz, auto selection

Output frequency range

:

nominal ± 5% with mains synchronizing

Output waveform

:

sine wave

Harmonic distortion

:

< 3% with linear load, < 5% with non-linear full load

Power factor at nominal input voltage

:

0.87

0.8

0.86

0.92

Crest factor (peak to RMS current)

:

≤ 3 : 1

Capacity appliance outlets

:

with 55A Terminal Block

Bypass

AC input voltage range

:

± 15% of selected output voltage

Frequency tracking rate

:

1Hz/s

Frequency tracking range

:

± 5% of selected frequency

Typical transfer time, msec

:

0

Overload capability

:

fully protected against overload and short circuits

Overload behavior during battery operation

:

130% during 10 seconds

130% during 1 minute

:

200% during 2 seconds

200% during 5 seconds

Overload behavior during bypass operation

: depends on rating of thermal circuit breaker

overload protection

125% of TCB value for 200 seconds

110% for 300 seconds

200% of TCB value for 10 seconds

130% for 30 seconds

300% of TCB value for 4 seconds

200% for 5 seconds

Batteries (ratings given for 25ºC)

Nominal voltage (Vdc)

:

144

144

288

288

Number / Ah batteries

(in battery kit and battery ext. pack)

:

12pcs / 8Ah

12pcs / 8Ah

24pcs / 8Ah

24pcs / 8Ah

Type :

REW45-12

FR

Service life

:

up to 5 years (depending on use)

Recharge current

:

1 A

Battery recharge time

(batt. discharged at 100% load)

:

6 hours for 90% capacity

3 hours for 90% capacity

Runtime in minutes

at typical load (75%)

:

8

8

9

9

25%

:

31 31 40 40

50%

:

14 14 16 16

75%

:

8 8 9 9

100%

:

5 5 5 5

General

Weight UPS kg

:

30.3 Kg (67 lbs)

49.3 Kg (109 lbs)

Dimensions UPS (h

x

w

x

d)

: 176x430x592 mm (6.9x16.9x22.55 in)

267x430x660 mm (10.5x16.9x26 in)

Weight battery pack kg

:

43 Kg (94.7 lbs)

91 Kg (200.4 lbs)

Dimensions battery pack

: 87x430x592 mm (3.47x16.9x2255 in)

173x430x660 mm (6.8x16.9x26 in)

Enclosure / protection

:

steel-plastic

/

IP20

Environment

Safety :

UL1778

Electromagnetic compatibility

:

EMI: FCC CFR47 Part 15, class A, ESD: IEC61000-4-2, level 4

RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4, level 4, Surge: IEC61000-4-5, level 3

ANSI C62.41 (IEEE587) Category A (level 3) & B (level 1)

Ambient temperature

:

0 to +40ºC

Audible noise at 1 meter

:

< 55 dB(A), load and temperature dependent

Max. relative humidity

:

90% (non-condensing)

Color

:

Black - RAL 9005