GEI-100431
——————
BYTE ASSIGNMENT
——————
3
28
3.2.2.6.1.3 Write DGF parameter - Reply Error
If the writing of the DGF parameter is rejected, the response is:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service
Code
33hex OR
80hex
Set DGF Parameter
Reply code- Object
Specific Service
Word
Result
XXXX
1)
DGF specific error code
dn3975ge
1) For error codes see DGF-manual.
3.2.1.6.2 Read DGF parameter
In this example the reading of a DGF-parameter is shown; the cases of positive
or wrong reading are distinguished.
3.2.1.6.2.1 Read DGF Parameter Request
The data frame for the reading of a DGF parameter is composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service
Code
32hex
Get DGF Parameter -
Object Specific Service
See Note
1)
Class ID
67hex
DGF Parameter Access
Class Object
Word
Instance
ID
XXXX
DGF Parameter Index in
format Low byte-High
byte
Byte
Data Type
2)
XX
DGF specific data type
code
Byte
N/U
0
Not used; has to be set to
zero
dn3980ge
1) Byte or Word depending on the type of allocation executed by the Master.