Troubleshooting procedure, Purpose, Cabinet alarm – GE Industrial Solutions GPS2436 User Manual

Page 95

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

95

Troubleshooting Procedure

Purpose

The troubleshooting procedure described below is used when a trouble condition has

been identified and a technician has been dispatched to the system as a first step in

diagnosing and correcting the problem.

For all trouble conditions, proceed as follows:

Cabinet Alarm

1.

Locate the Galaxy controller. When a trouble condition exists, the red alarm on the

top of the cabinet will be illuminated and the display screen on the controller will

typically have LED’s illuminated. See Figure 12-1.

Figure 12-1: Location of cabinet alarm indicators

2.

Determine the system status. For most problems, one or more alarm and status

LEDs will be illuminated. Depending on the controller type, the following will be

displayed:

system voltage

system current

system mode

system number of alarm/warnings

If the screen is blank, but alarm and status LEDs are illuminated, call technical

support.

If the entire panel is blank, check the controller fuses. Verify that the controller is

getting power. If not, replace fuse. If the display is still blank, call technical support.

3.

To view the Alarms Menu: If the default screen appears normal, press the MENU

button. The main menu appears with “Alarms” blinking. Press ENTER to obtain the

Alarms menu. Additional data appears that will help to identify the problem.