3 SETUP

3.1 CONTROL PANEL – GRAPHIC DISPLAY

Fig. 3.1-1 Control panel – graphic display: UPS functioning in IEMi Operation Mode


Key to switch the Inverter ON ( I )

NOTE !

When IEMi Operation Mode is enabled, control of Inverter status
and selection of the feed path is done autonomously by the UPS
control logic.
Therefore, Inverter ON / Inverter OFF commands are disabled
when IEMi Operation Mode
is enabled.

Key for Inverter shutdown ( O )
Press the key to transfers the Load to Utility/Mains.
Keep pressed for 5 seconds to shutdown the Inverter.
This key is also used as the EPO (Emergency Power Off) reset.

NOTE !

Inverter OFF command is disabled when IEMi Operation Mode is
enabled. Furthermore, all functions associated with the ( O )
key
are disabled – including the EPO
reset.

Modifications reserved

Page 6/24

OPM_OPT_IEM_iXX_XXX_XGB_V010.doc

User Manual IEMi - Intelligent Energy Management integrated