1 – output voltage 277vac – GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual
Page 20
modifications reserved
OPM_LPU_11U_6K0_10K_1US_V010.Doc
19
User manual LP11 924 6 & 10 kVA UPS 1.0
4.5.3 - AVAILABLE OUTPUT VOLTAGES: HARDWARE MODIFICATIONS
The following output voltages are available: 120, 208, 220, 230, 240, 277 Vac. An insertion bridge is placed between
terminals 2 and 3. An extra insertion bridge was delivered with the unit (in a plastic bag) to enable other output voltages.
4.5.3.1 – OUTPUT VOLTAGE 277VAC
The off-factory setting is 277VAC; make sure the following steps are implemented:
1. An insertion bridge is placed between terminals 2 and 3.
2. The output tap is set at 277VAC: Please refer to fig.11 and 11a and check the following.
White wire W is connected to faston 67 (connect) on Printed Circuit Board (PCB) part 1113-C
Brown wire F is connected to faston 65 (park) on PCB part 1113-C
Yellow wire L is connected to faston 66 (park) on PCB part 1113-C
3. Connect the output wires to the terminals 1 (L1) and 4 (L2) and ground wire to terminal 5. Ground connection is
essential! See figure 11b.
4. Return to either section 4.5.1.1 step 5 or section 4.5.1.2 step 5. Pay special attention to step 11 in these sections,
i.e. do not forget to modify the display software as described in section 4.5.4.
Output tap changed to 208 Volt
Output tap changed to 240 Volt
Output tap factory setting 277 Volt
Figure 11. LP11 924 6&10 kVA: Output tap change
Figure 11a. LP11 924 6&10 kVA: Rear View
Figure 11b. LP11 924 6&10 kVA: 277 Vac output connection