GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual
Page 36
modifications reserved
OPM_LPU_11U_6K0_10K_1US_V010.Doc
35
User manual LP11 924 6 & 10 kVA UPS 1.0
After 24 hours of charging time, the battery voltage did not reach the normal float 
voltage. This may be caused by faulty batteries, too many battery packs connected or 
a charger fault.
BATTERY CHARGERY 
NO FLOAT 
The main DC-capacitor needs replacement due to aging or failure.
CAPACITOR C1 
CAPACITY LOW 
Due to a failure the output converter's output is not available. As a result the load may 
have been transferred to bypass.
LOADnotPROTECTED 
INVERTER OFF 
The remaining runtime is zero. As a result the load may have been transferred to
bypass.
LOADnotPROTECTED 
BATTERY DEPLETED 
The remaining run time is less than the set time (standard 2 minutes). This text
alternates with the following screen:
LOADnotPROTECTED 
BATTERY LOW 
UPS SHOUTDOWN 
LEFT 2 MINUTES 
The output voltage can be lost after the indicated time due to discharged battery.
Controlled shutdown of any computer equipment is absolutely necessary at this point. 
(Using the RS232 or SNMP communications interface, this procedure can be initiated 
automatically on unattended systems). If the UPS operates at 100% load, the
shutdown procedure should be completed within 2 minutes after the 'battery low' 
alarm started. When the batteries are fully discharged, the UPS is no longer able to 
power the connected equipment.
The static bypass circuit breaker (rear panel, 9) is in 'off' (down position): no bypass
voltage available. Utility voltage is available. If not manually operated, this may have 
been caused by an overload situation.
BYPASS ERROR 
FUSE FAILURE 
The utility circuit breaker (rear panel, 8) is in the 'off' (down position): no line voltage 
available, bypass voltage is available. If not manually operated, this may have been 
caused by an internal system failure.
INPUT ERROR 
FUSE FAILURE 
The internal battery fuse is defective; this may have been caused by an internal system
failure. This alarm also appears if no batteries are installed.
INTERNAL BATTERY
FUSE FAILURE
The external battery has been disconnected from the system: its energy reserve is not 
available. See section 4.5.5 step 7 for details.
EXTERNAL BATTERY 
FUSE FAILURE 
The batteries are (almost) chemically worn out. If the batteries are aged, they must be 
replaced as soon as possible to ensure full protection for your equipment (see section 8.4).
REPLACE BATTERY
The utility voltage and/or utility frequency are outside UPS input tolerance (see chapter 
10, specifications).
INPUT out LIMITS 
137V 60.0Hz 
The utility voltage and/or utility frequency are outside bypass input tolerance but 
inside UPS (rectifier) input tolerance (see chapter 10, specifications). Bypass operation 
is inhibited: if for whatever reason the output converter is unable to deliver the 
required output, output power is lost.
BYPASSoutLIMITS 
197V 60.0Hz