Asus RS724Q-E6/RS12 User Manual

Page 38

Advertising
background image

Chapter 2: Hardware setup

2-18

3. Firmly pull the power supply

module out of the system chassis.

4. Firmly push the new power supply

module into the chassis until the

latch locks to the server chassis.

• If you install two or more nodes, please install both the power supply

modules.

• The system automatically combines the two power supply modules as a

single one. The combined output power varies with input voltages. Refer to

the table below for details.

Input Voltage

Max. Output Power (Watt) per PSU

100–120Vac, 12–10A, 50–60Hz 1000W

120–140Vac, 12–10A, 50–60Hz 1200W

180–240Vac, 10.5–8A, 50–60Hz 1620W

• To enable the hot-swap feature (redundant mode), keep the total power

consumption of the installed nodes under the maximum output power of an

individual power supply module.

• For steady power input, use only the power cables that come with the

server system package.

Advertising